Frequently asked questions

Cooling tower and water treatment questions.

Straight answers from our engineers on servicing, cleaning, treatment and filtration.

01 — Questions

Cooling tower maintenance

How often should a cooling tower be serviced?

Most commercial and industrial cooling towers on a chemical treatment programme are visited monthly. Each visit tests the water against its control limits, adjusts the dosing and bleed-off settings and records the results in a written report.

Critical sites such as hospitals and semiconductor fabs often add more frequent checks between visits. Physical cleaning is scheduled separately (see below).

How often should a cooling tower be cleaned?

A full physical clean (drain-down, basin desludging, fill and drift eliminator cleaning and disinfection before refill) is commonly done once or twice a year.

Towers on dusty sites or near construction and towers with a high bacteria or Legionella result usually need it more often. We recommend a frequency after inspecting the tower and its water history.

How long does a cooling tower last?

With good water treatment and maintenance, a factory-assembled FRP cooling tower commonly lasts around 15 to 20 years and field-erected towers can last longer. Fill media usually needs replacing sooner, often within 5 to 10 years, depending on fouling and water quality.

Poor treatment shortens both: scale and biofilm clog the fill, corrosion attacks metal parts and sludge builds up in the basin.

What happens during a maintenance visit?

Our technician tests the make-up and recirculating water on site, checks the dosing pumps, chemical levels and conductivity controller, inspects the tower and basin and adjusts the programme where readings drift. You receive a written service report after every visit.

02 — Questions

Water treatment

What are cycles of concentration?

Cycles of concentration compare the dissolved solids in the recirculating water with those in the make-up water. As water evaporates, solids concentrate; bleed-off removes some of that water to keep them below the point where scale forms.

Higher cycles mean less bleed-off and less make-up water. A matched inhibitor programme with conductivity-controlled bleed-off lets a tower run at higher cycles safely. In one hotel case we moved a tower from 3.2 to 8 cycles and cut make-up water by 28%.

Why use both oxidising and non-oxidising biocides?

Oxidising biocides such as bromine-based products kill bacteria quickly and are dosed routinely. Non-oxidising biocides work differently and reach organisms protected inside biofilm.

Alternating the two (a dual-biocide programme) gives broader control and reduces the chance of bacteria adapting to a single product. It is the approach we use where Legionella risk is high, such as hospitals and hotels.

How often should cooling tower water be tested for Legionella?

A common schedule is monthly on-site dip-slide testing for total bacteria with laboratory Legionella testing every quarter. Higher-risk sites and towers that return a positive result are tested more often until results are back under control.

One of our hospital sites on this schedule recorded zero positive Legionella samples over 24 months.

Can I buy treatment chemicals without a service contract?

Yes. As an authorized Kurita distributor we supply chemicals on their own. Most sites get better results with testing included, because the dose needs to follow the water and the load, so we usually recommend at least a monthly testing visit.

03 — Questions

Chilled water & process cooling

What is a closed loop chilled water system?

A closed loop circulates the same water between the chillers and the air handling units or process equipment, with very little make-up. Because the water is not exposed to air like a cooling tower, the risks are different: corrosion of steel and copper, sludge from corrosion products and bacteria that thrive in low-flow sections.

How often should a closed loop be tested?

Monthly testing is typical for most closed loops. We check inhibitor level, pH, conductivity and iron and copper levels for signs of corrosion and look for bacteria. Any sudden rise in make-up water is a warning sign of a leak and is investigated straight away.

What is a Cetamine® programme?

Cetamine® is a Kurita water treatment technology based on film-forming amines. It forms a thin protective film on metal surfaces in the loop, which limits corrosion across mixed-metal systems. We combine it with microbial control and routine monitoring for closed chilled water loops.

What is condenser approach temperature and why does it matter?

Approach temperature is the difference between the refrigerant condensing temperature and the condenser water leaving temperature. A clean condenser has a low approach. Scale, sludge and biofilm in the tubes push it up, so the compressor works harder. Each 1 °C rise in condensing temperature adds roughly 2–3% to compressor energy.

What is process cooling water (PCW) in a semiconductor fab?

Process cooling water is a closed loop that removes heat from process tools and equipment at a tightly controlled temperature and pressure. The heat is rejected through heat exchangers to the chiller and cooling tower system. Because tools depend on it, PCW quality and stability directly affect yield and uptime.

Can treatment be done without stopping production?

Routine treatment, dosing adjustments and testing are all done online while the plant runs. Work that needs a system out of service, such as condenser tube flushing, is planned with your facilities team for a scheduled window.

04 — Questions

Side stream filtration

What is side stream filtration for a cooling tower?

Side stream filtration takes a portion of the tower's recirculating water, typically 5–10% of the flow, passes it through a filter to remove suspended solids and returns it to the basin. This reduces fouling, under-deposit corrosion and microbial growth and helps keep chiller efficiency up.

How much side stream filtration flow do I need?

A common design basis is 5–10% of the recirculation flow rate. A system recirculating 500 m³/h would typically need 25–50 m³/h of side stream filtration. Dust load, basin design and water quality affect the final size; send us your flow rate and we will size it.

What is the difference between a screen filter and a sand filter?

A screen filter traps particles on a mesh screen. On the VAF V-Series it is rated from 10 to 1500 micron and cleans itself with a short automatic flush. A sand filter traps particles in a bed of media and is backwashed periodically, which uses more water and space.

Do you supply Xylem / Evoqua VAF filters in Malaysia?

Yes. Oasis is the authorized Xylem distributor for Southeast Asia for side stream filtration, including Evoqua VAF™ V-Series self-cleaning screen filters such as the V-200P and V-1000. We supply, install and service them in Malaysia.

05 — Questions

Working with Oasis

Which areas of Malaysia do you cover?

We service sites across Malaysia from our Penang headquarters and our Selangor office in Shah Alam. That includes Penang, Kedah and the northern region, Selangor and Kuala Lumpur and Johor. Filtration supply covers Southeast Asia.

How do you price water treatment?

Every site is quoted individually after readings, because the programme depends on your water, your equipment and your load. We start with a site survey and water analysis and send a written proposal.

Speak to an engineer.

We sample your make-up and recirculating water, inspect the tower and condenser and return a written treatment proposal.

HQ
Penang
354-H, Jalan Jelutong, Jelutong, 11600 Jelutong, Pulau Pinang
04-281 2648
Office
Selangor
No. 48, Jalan Bulan U5/167, Seksyen U5, Bandar Pinggiran Subang (Subang 2), 40150 Shah Alam, Selangor
03-7859 7648
Email
General enquiries
Services across Malaysia. Filtration distributorship across Southeast Asia.
info@oasis-eng.com.my