Measured results
Cooling water treatment case studies.
Before and after, measured on site: condenser approach temperature, cycles of concentration, make-up water and Legionella results. Client names are withheld.
01 — Semiconductor fab · Tube flushing · 3 chillers
Condenser approach temperature restored on LT and MT chillers
Two low-temperature and one medium-temperature chiller at a semiconductor fab were cleaned and put on a treatment programme. Approach temperature was logged per chiller before and after.
3.6 → 0.5 °CAverage condenser approach, before → after
85.6%Average improvement across 3 chillers
02 — Hotel · Cooling tower programme
Cooling tower programme and bleed-off automation
Manual blowdown was replaced with conductivity-controlled bleed-off and a revised inhibitor programme.
3.2 → 8Cycles of concentration
28%Reduction in make-up water
03 — Hospital · Microbiological control
Microbiological control for rooftop cooling towers
A dual-biocide programme with monthly dip-slide and quarterly laboratory Legionella testing.
0Positive Legionella samples, 24 months
< 10³CFU/mL total bacteria, all visits