Measured results

Cooling water treatment case studies.

Before and after, measured on site: condenser approach temperature, cycles of concentration, make-up water and Legionella results. Client names are withheld.

01 — Semiconductor fab · Tube flushing · 3 chillers

Condenser approach temperature restored on LT and MT chillers

Two low-temperature and one medium-temperature chiller at a semiconductor fab were cleaned and put on a treatment programme. Approach temperature was logged per chiller before and after.

3.6 → 0.5 °CAverage condenser approach, before → after
85.6%Average improvement across 3 chillers

Read the case study →

02 — Hotel · Cooling tower programme

Cooling tower programme and bleed-off automation

Manual blowdown was replaced with conductivity-controlled bleed-off and a revised inhibitor programme.

3.2 → 8Cycles of concentration
28%Reduction in make-up water

Read the case study →

03 — Hospital · Microbiological control

Microbiological control for rooftop cooling towers

A dual-biocide programme with monthly dip-slide and quarterly laboratory Legionella testing.

0Positive Legionella samples, 24 months
< 10³CFU/mL total bacteria, all visits

Read the case study →

Speak to an engineer.

We sample your make-up and recirculating water, inspect the tower and condenser and return a written treatment proposal.

HQ
Penang
354-H, Jalan Jelutong, Jelutong, 11600 Jelutong, Pulau Pinang
04-281 2648
Office
Selangor
No. 48, Jalan Bulan U5/167, Seksyen U5, Bandar Pinggiran Subang (Subang 2), 40150 Shah Alam, Selangor
03-7859 7648
Email
General enquiries
Services across Malaysia. Filtration distributorship across Southeast Asia.
info@oasis-eng.com.my