Case study · Semiconductor fab · Tube flushing · 3 chillers
Condenser approach temperature restored on LT and MT chillers.
Two low-temperature and one medium-temperature chiller at a semiconductor fab were cleaned and put on a treatment programme. Approach temperature was logged per chiller before and after.

- Average condenser approach, before → after
- 3.6 → 0.5 °C
- Average improvement across 3 chillers
- 85.6%
What we found.
Condenser approach temperature had climbed on three chillers serving the fab: two low-temperature (LT) units and one medium-temperature (MT) unit. A high approach means scale, sludge or biofilm in the condenser tubes is insulating heat transfer, so the compressor runs at a higher head pressure and uses more energy for the same cooling. Each 1 °C rise in condensing temperature adds roughly 2–3% to compressor energy.
What we did.
- Approach temperature and water readings logged per chiller before work
- Condenser tubes cleaned to restore heat transfer
- Chillers put on an ongoing water treatment programme to hold the result
- Approach temperature logged per chiller after cleaning
Measured before and after.
Average condenser approach fell from 3.6 °C to 0.5 °C, an average improvement of 85.6% across the three chillers. The treatment programme that followed keeps scale and biofilm from rebuilding between cleans.
Client name withheld. Figures measured on site and reported to the client.
The services behind this result.
Semiconductor PCW treatment
Process cooling water and chiller plant care for fabs and assembly plants.
Learn more →02Chilled water treatment
Closed loop corrosion and microbial control with Kurita Cetamine® programmes.
Learn more →03All six services
Chemical dosing, dosing systems, bleed-off control, filtration, loop flushing and tower cleaning.
Learn more →04Condenser loop flushing
The service used on this job, on our services page.
See the service →