Scale, corrosion and microbiological control programmes matched to your make-up water and cycles of concentration, using Kurita chemistry and monitored by our own technicians every month.

- Chemistry
- Kurita, Japan & Europe
- Biocides
- Oxidising & non-oxidising
- Legionella
- Dip-slide monthly · lab quarterly
- Control
- Conductivity bleed-off
Scale, corrosion and biological growth.
Scale
Evaporation concentrates calcium and other minerals until they precipitate on the hottest surfaces: condenser tubes and fills. A thin layer of scale cuts heat transfer and pushes up approach temperature. Scale inhibitors keep minerals in solution so the tower can run at higher cycles.
Corrosion
Warm, aerated and concentrated water attacks mild steel, galvanised steel and copper. Corrosion products then deposit elsewhere in the loop. Corrosion inhibitors protect the metals in your system and are dosed to a measured residual.
Microbiological growth
Cooling towers are warm, wet and full of nutrients. Bacteria form biofilm that insulates tubes, shelters Legionella and causes under-deposit corrosion. Oxidising and non-oxidising biocides are alternated to keep counts down and biofilm off.
Legionella control
Legionella multiplies in sludge and biofilm and spreads in the tower's drift. Control combines biocides, a physically clean tower and routine testing: monthly dip-slides on site and quarterly laboratory Legionella tests.
A cooling tower water treatment programme.
Built around your water analysis, not a standard dose.
| Chemistry | Kurita (Japan & Europe) |
|---|---|
| Control | Conductivity µS/cm, auto bleed-off + dosing interlock |
| Monitoring | Monthly on site; lab Legionella quarterly |
| Reporting | Written report each visit |
- Analysis of make-up and recirculating water to set control limits and cycles
- Kurita scale and corrosion inhibitors matched to your water and metallurgy
- Dual-biocide programme with oxidising and non-oxidising biocides
- Automated dosing and conductivity-controlled bleed-off
- Monthly site visit with on-site testing and adjustment
- Monthly dip-slides and quarterly laboratory Legionella testing
- Written service report after every visit with results trended against control limits
You are dosing by hand or by timer, the tower runs at low cycles to be safe or a bacteria result came back high.
Treatment you can see in the numbers.
From cooling tower programmes we run.
Hospital · Microbiological control
Microbiological control for rooftop cooling towers
What works alongside chemical treatment.
Side stream filtration
Xylem VAF™ self-cleaning screen filters, sized and installed by Oasis.
Learn more →02Cooling tower maintenance
Monthly servicing, physical cleaning and Legionella control for cooling towers across Malaysia.
Learn more →03Chilled water treatment
Closed loop corrosion and microbial control with Kurita Cetamine® programmes.
Learn more →04Process cooling water treatment
Industrial cooling towers and process chilled water loops under variable load.
Learn more →Cooling tower water treatment: common questions.
What are cycles of concentration?
Cycles of concentration compare the dissolved solids in the recirculating water with those in the make-up water. As water evaporates, solids concentrate; bleed-off removes some of that water to keep them below the point where scale forms.
Higher cycles mean less bleed-off and less make-up water. A matched inhibitor programme with conductivity-controlled bleed-off lets a tower run at higher cycles safely. In one hotel case we moved a tower from 3.2 to 8 cycles and cut make-up water by 28%.
Why use both oxidising and non-oxidising biocides?
Oxidising biocides such as bromine-based products kill bacteria quickly and are dosed routinely. Non-oxidising biocides work differently and reach organisms protected inside biofilm.
Alternating the two (a dual-biocide programme) gives broader control and reduces the chance of bacteria adapting to a single product. It is the approach we use where Legionella risk is high, such as hospitals and hotels.
How often should cooling tower water be tested for Legionella?
A common schedule is monthly on-site dip-slide testing for total bacteria with laboratory Legionella testing every quarter. Higher-risk sites and towers that return a positive result are tested more often until results are back under control.
One of our hospital sites on this schedule recorded zero positive Legionella samples over 24 months.