Xylem distributor · Southeast Asia
Side stream filtration for cooling towers.
Self-cleaning Xylem VAF™ screen filters that take suspended solids out of your cooling water continuously, sized, supplied and installed by the authorized Xylem distributor for Southeast Asia.

- Flow
- 5–10% of recirculation
- Screens
- 10–1500 micron, 316L SS
- Cleaning
- Automatic, DP-triggered
- Coverage
- Malaysia & Southeast Asia
What side stream filtration prevents.
A cooling tower scrubs dust and debris out of the air it moves. Those suspended solids settle in condenser tubes and the basin, insulate heat transfer surfaces, cause under-deposit corrosion and shelter bacteria from the biocide.
Side stream filtration takes 5–10% of the recirculating flow, filters it and returns it to the basin. Over time the whole system volume passes through the filter, so solids are removed continuously instead of building up between cleans. The result is cleaner water, better biocide performance and less bleed-off.
Xylem VAF™ V-Series self-cleaning screen filters.
Automatic self-cleaning screen filters that flush themselves when the screen loads up and stay online while they do it. Data sheets on the product page.
| Sizing | 5–10% of recirculation flow |
|---|---|
| Install | Supply, piping tie-in, commissioning |
| Control | DP-triggered auto flush, linked to dosing controller |
| Distributor | Authorized Xylem, Southeast Asia |
- V-200P: 7–50 m³/h per filter, glass-reinforced nylon body, 3″ inlet and outlet, water motor drive needs no electrical power for cleaning
- V-1000: 14–374 m³/h per filter, 316L stainless steel body with 6″ or 8″ flanges for larger flows
- Screens from 10 to 1500 micron in 316L stainless steel
- Automatic flush when differential pressure reaches 0.5 bar, using about 15 L (V-200P) or 57 L (V-1000) per flush
- Stays in service while flushing, with no manual backwashing
Your basin is muddy, the site is dusty, turbidity is high or condenser tubes foul quickly after cleaning.
From flow rate to commissioning.
- 01
Sizing
Send us your recirculation flow rate and basin details. We size the filter to 5–10% of the flow and the site's dust load.
- 02
Supply and tie-in
We supply the filter and connect it to the recirculating line and basin return.
- 03
Commissioning
We set the differential-pressure auto flush and link it to your dosing controller.
Related services and products.
Kurita chemicals & Xylem filters
Data sheets and specifications for the products we supply.
Learn more →02Cooling tower chemical treatment
Scale and corrosion inhibitors, oxidising and non-oxidising biocides and Legionella control.
Learn more →03Cooling tower maintenance
Monthly servicing, physical cleaning and Legionella control for cooling towers across Malaysia.
Learn more →04Process cooling water treatment
Industrial cooling towers and process chilled water loops under variable load.
Learn more →Side stream filtration: common questions.
What is side stream filtration for a cooling tower?
Side stream filtration takes a portion of the tower's recirculating water, typically 5–10% of the flow, passes it through a filter to remove suspended solids and returns it to the basin. This reduces fouling, under-deposit corrosion and microbial growth and helps keep chiller efficiency up.
How much side stream filtration flow do I need?
A common design basis is 5–10% of the recirculation flow rate. A system recirculating 500 m³/h would typically need 25–50 m³/h of side stream filtration. Dust load, basin design and water quality affect the final size; send us your flow rate and we will size it.
What is the difference between a screen filter and a sand filter?
A screen filter traps particles on a mesh screen. On the VAF V-Series it is rated from 10 to 1500 micron and cleans itself with a short automatic flush. A sand filter traps particles in a bed of media and is backwashed periodically, which uses more water and space.
Do you supply Xylem / Evoqua VAF filters in Malaysia?
Yes. Oasis is the authorized Xylem distributor for Southeast Asia for side stream filtration, including Evoqua VAF™ V-Series self-cleaning screen filters such as the V-200P and V-1000. We supply, install and service them in Malaysia.